TYPICAL WIRING1F95-1280/1F95-1291
1F95-1280 INSTALLER/CONFIGURATION MENU (cont.)
To enter the menu: Press the Menu touch key. Press and hold for 5 seconds the Installer Config touch key. This displays
menu item #1 in the table below. Press
to advance to the next menu item or to return to a previous menu item. Press
or
to change a menu item option.
1F95-1291 INSTALLER/CONFIGURATION MENU
CONFIGURATION MENU
Menu
Reference
Number
Program-
mable
Non-
Program-
mable
Press
key
Displayed
Factory
(Default)
Press or
to select from
listed options COMMENTS
1 1 1 MS 2
HP 1, HP 2, SS 1
Selects Multi-Stage (MS2, No Heat Pump), Heat Pump 1
(HP1, 1 compressor), Heat Pump 2 (HP2, 2 compressor
or 2 speed compressor), or Single Stage.
222
GAS (ELE)
GAS setting: furnace controls blower.
ELE setting: thermostat controls blower.
333
ob (O) b
Selects Reversing Valve (This item is only to appear if HP1 or HP2 is
selected above.)
443
(7) Days, P5 or 0
Programs per week. (5=5-1-1 or 0 = non-programmable)
5 5 NA
(4) PS 2 Programs per day.
4 = Morning, Day, Evening, Night
2 = Day, Night
664
Cool-Off-
Heat-Auto
Cool-Off-Heat, Heat Off,
Heat, Cool-Off, Auto Off
System switch configuration in non heat pump mode.
Cool-Off-Heat-
Em-Auto
Cool-Off-Heat-Em,
Off-Em-Auto
System switch configuration, heat pump mode.
77NA
(On) E
OFF Selects Energy Management Recovery, E (with programming option
on)
885
(FA) Heat, Cr SL
Selects Adjustable Anticipation, cycle rate, Heat
996
(FA) Cool, Cr SL
Selects Adjustable Anticipation, cycle rate, Cool
10 10 7
Cr/AU, Em (FA) SL
Selects Adjustable Anticipation, cycle rate auxiliary, (This item is
only to appear if HP1 or HP2 is selected above).
11 11 8
(OFF) CL On
Selects Compressor Lockout.
12 12 9
(On) dL OFF
Selects Continuous Display backlight.
13 13 10
(LO) dL HI
Selects Backlight Intensity.
14 14 11
0
(temperature)
5, LO to 5, HI
Selects Adjustable Ambient Temperature Display [range -5 (LO) to
+5 (HI)].
15 15 12 °F
(temperature)
°C Selects °F/°C Display (temperature units in Fahrenheit or Celsius).
16 16 13
(On) b OFF
Selects audible Beeper On/Off.
CONFIGURATION MENU
Menu
Reference
Number
Program-
mable
Non-
Program-
mable
Press
key
Displayed
Factory
(Default)
Press
or
to select from
listed options COMMENTS
28
(cont.)
28
(cont.)
26
(cont.)
(OFF) dF On Selects Dual Fuel feature using outdoor sensor On or OFF (This item
appears if HP1 or HP2 is selected and outdoor sensor is installed and
enabled.
28 28 26
(35) dF 5-50 Selects Dual Fuel setpoint (°F) with outdoor sensor available.
(60) Cd 0-99 Selects compressor delay in seconds.
29 29 27
(80) AO 35-74 Selects Auxiliary Heat cut out temperature. This item appears if HP1
or HP2 is selected and outdoor sensor is installed and enabled.
30 30 28
(80) bP 79-20 Not used
31 31 NA
(o) PP 1, 2, 3 Select Pre-occupancy purge.
32 32 NA
(OFF) EC ON Select Economizer or Damper Operation (default)
33 33 29
(OFF) Change
UV Lamp
On Selects Change UV Lamp feature.
350 Days 25-1975 Change UV Lamp duration days.
34 34 30
OFF
Change Filter
On Selects Change Filter feature.
200 Hrs 25-1975 Change Filter duration hours.
www.white-rodgers.com